The Ad-NeT network system allows all MxPro 5 series control panels, remote terminals & network peripherals to be connected together with 2 core cable (Read more)
PRODUCT DETAILS
The Ad-NeT network system allows all MxPro 5 series control panels, remote terminals and network peripherals to be connected together using standard fire resistant two-core cable. It provides both the benefits of distributed intelligence and reduced installation costs whilst catering for the smallest two-panel network through to the largest 200 panel wide area networked system.
The network operates as a true peer-to peer system allowing information from any input or output device to be passed over the network and displayed on any MxPro 5 control panel or remote terminal as required.
Simply adding and connecting a network card allows any MxPro 5 control panel or remote terminal to be networked. All other nodes on the Ad-NeT system will be instantly aware of a panel as soon as it is given a valid network node address, allowing additional panels to be added at any time. All panels incorporate a network analyser providing valuable diagnostic and status information and also have the facility to prevent the transmission of fires or faults during commissioning.
For more complex systems, the Windows based PC-NeT Mx
configuration software allows sector based programming for Mute,
Silence, Resound and Reset control keys as well as investigation
delays, group
disablement and test instructions. All panels within the same
sector will share common controls and each panel or remote terminal
can also be programmed to show specific network information on a
zonal basis. For cause and effect, any input device can be
programmed to operate any output device on any panel.
Features:
- Large Ad-NeT+ 200 Panel Network
- Up to 1.5Km between Control Panels
- Windows based PC setup
- Network Systems share up to 1000 zones
- Network Analysis from Control Panel
Specifications |
|
Network Connections |
IN: A/B SCN(Screen) OUT: A/B SCN (Screen) |
On-board Indication |
2 Red LED’s. LED 1 illuminates when data is transmitted LED 2 illuminates when data is received |
Supply Current |
Mxp-503 Standard Network card: 20mA Mxp-509 Fault tolerant Network Card: 61mA (All power taken directly form the panel motherboard) |
Temperature range and Humidity |
-5°C to 40C 95% non-condensing (maximum) |
Recommended Cable |
2 Core twisted-pair plus screen |
Videos |
---|
No videos available |
Files |
---|
Advanced Electronics Network Card Datasheet |
Links* |
---|
Advanced website |
* External websites provide additional content that supports the content on connectec.uk however the external Web site is subject to change and is beyond the control of Connectec Ltd. Connectec cannot guarantee the accuracy of content on external websites and does not endorse the information or products on any external websites. You will be subject to the external websites own privacy policy when you follow these links.
Get expert answers to questions specific to this product below or for more help visit our Q&A forum
Be the first to ask a question and help others interested in this product
Read customer reviews or submit your review of this product
Your feedback helps us improve our products and services as well as helping other users make informed buying decisions.
There are no reviews for this product.
Why buy from Connectec?
SUPPORT
Our technical support team are experienced installation engineers with years of field experience.
SERVICE
Customer service is our top priority. We always try to ensure we offer a first class service too all our customers.
DELIVERY
We offer FREE mainland UK delivery on orders over £75 and FREE next day delivery on orders over £150*.
PARTNERS
We are approved resellers for direct access to manufacturer warranty and support.
* Qualifying products only, subject to terms. For more information view our delivery information.