Apollo XP95 Manual Call Point Surface with isolator - Red
The Apollo 55100-908APO is a manual XP95 call point with built-in isolator, and is designed to work on a loop of intelligent fire detection devices. (Read more)
PRODUCT DETAILS
The Apollo 55100-908APO is a manual call point with a built-in isolator, that is part of the XP95 range, and is designed to work on a loop of intelligent fire detection devices. When activated, it interrupts the polling cycle for a very fast response.
The XP95 Manual Call Point has an easily resettable element rather than a break glass. It also features a unique ‘Plug and Play’ installation concept designed specifically to reduce installation time. The call point utilises a terminal block, where all installation cabling is terminated.
Features:
- EN 54-11 & EN 54-17 Certified
- Built-in Isolator
- Reports an alarm in under 0.2 seconds
- 'Plug and Play' terminal connections for faster wiring
- Continuity link for wiring test before commissioning
- Suitable for semi flush or surface mounting
- XP95 & Discovery compatible
General |
|
Warranty |
10 years |
Mechanical |
|
Colour |
Red |
Weight |
151g |
Materials housing |
Polycarbonate ABS |
Product length |
93mm |
Product width |
89mm |
Product depth |
26.5mm |
Detection principle |
Operation of a switch |
Conformance |
|
Standards |
EN 54-17 |
Approvals |
LPCB CPR |
Electrical |
|
Protocol voltage (max) |
9V |
Protocol voltage (min) |
5V |
Protocol voltage |
5 to 9V peak to peak |
Power-up surge current |
1mA |
Maximum power-up time |
1 second |
Quiescent current |
100μA |
Quiescent current tested at |
24V dc |
Environmental |
|
Humidity (max) |
95% RH |
Humidity (min) |
0% RH |
Humidity |
0% to 95% (no condensation or icing) |
Humidity Note |
no condensation or icing |
Operating temperature (min) |
-20°C |
Operating temperature (max) |
60°C |
Operating temperature |
-20 to 60°C |
IP rating Value |
IP24 |
Storage temperature (min) |
-30°C |
Storage temperature (max) |
80°C |
Storage temperature |
-30 to 80°C |
Operating temperature |
-4 to 140°F |
Operating temperature (max) |
140°F |
Operating temperature (min) |
-4°F |
Videos |
---|
Files |
---|
Apollo 55100-908APO Datasheet |
Apollo 55100-908APO Installation Guide |
Links* |
---|
Apollo website |
Apollo support site |
* External websites provide additional content that supports the content on connectec.uk however the external Web site is subject to change and is beyond the control of Connectec Ltd. Connectec cannot guarantee the accuracy of content on external websites and does not endorse the information or products on any external websites. You will be subject to the external websites own privacy policy when you follow these links.
Get expert answers to questions specific to this product below or for more help visit our Q&A forum
Be the first to ask a question and help others interested in this product
Read customer reviews or submit your review of this product
Your feedback helps us improve our products and services as well as helping other users make informed buying decisions.
There are no reviews for this product.
Why buy from Connectec?
SUPPORT
Our technical support team are experienced installation engineers with years of field experience.
SERVICE
Customer service is our top priority. We always try to ensure we offer a first class service too all our customers.
DELIVERY
We offer FREE mainland UK delivery on orders over £75 and FREE next day delivery on orders over £150*.
PARTNERS
We are approved resellers for direct access to manufacturer warranty and support.
* Qualifying products only, subject to terms. For more information view our delivery information.