C-TEC CFP708-2 CFP AlarmSense 8 Zone Two-Wire Fire Alarm Panel
C-TEC CFP708-2 CFP AlarmSense 8 Zone Two-Wire Fire Alarm Panel
C-TEC CFP708-2 CFP AlarmSense 8 Zone Two-Wire Fire Alarm Panel
swipe to view images
fullscreen

C-TEC CFP708-2 CFP AlarmSense 8 Zone Two-Wire Fire Alarm Panel

Rated 0/5   0 reviews | 1 Questions
C-TEC logo C-TEC
  • Certified to EN54-2 & 4
  • 8 AlarmSense zones
  • 10 year guarantee
Link to videos

The C-TEC CFP 8 zone two-wire fire alarm panel has 8 AlarmSense zones and 4 conventional sounder circuits also including zone delays (Read more)

Loading
£275.04
£229.20 Ex VAT
In stock
Free delivery availale
Order before 15:30 for delivery from Tuesday 17th December
Product CodeCTE0009
ModelCFP708-2
More Information
RELATED PRODUCTS

PRODUCT DETAILS

C-TEC's range of CFP fire alarm panels are the UK's best selling two-wire fire panels. The C-TEC CFP 8 zone two-wire fire alarm panel offers an array of user and installer-friendly features at a very competitive price and are ideal for smaller budget oriented installations.

Supplied in a flush or surface mount plastic enclosure that does not require a bezel, it includes eight AlarmSense zones, four conventional sounder circuits, class change and alert inputs and on-board fire and fault relays.

A wide range of engineering functions are also provided including zone delays, coincidence and non-latching zone facilities.

Wiring Diagram

CFP708-2_Wiring_Diagram.png

Features

  • Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB)
  • Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry
  • Manufactured by C-TEC in the UK
  • Two AlarmSense zone circuits - compatible with Apollo's AlarmSense detectors, call points, sounders and visual indicators
  • Four conventional sounder circuits
  • Integral 1.5A EN54-4/A2 compliant switch mode PSU
  • Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones
  • Two on-board relays (Fire and Fault)
  • Two open-collector outputs (Remote and Reset)
  • 'Class change' and alert inputs
  • Installer-friendly design
  • Attractive flush or surface mountable plastic lid and enclosure - no bezel required
  • Low 25mA quiescent current
  • Multiple indicators
  • System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system)
  • Space for two x 12V 3.3Ah VRLA batteries
YOU MIGHT ALSO NEED
Loading
 
 
 
 
 
Loading
 
 
 
 
 
Loading
 
 
 
 
 
Loading
 
 
 
 
 
Loading
 
 
 
 
 
Loading
 
 
 
 
 
Loading
 
 
 
 
 
Loading
 
 
 
 
 
Loading
 
 
 
 
 
Loading
 
 
 
 
 
Loading
 
 
 
 
 
SPECIFICATIONS
Specification
Approvals/certifications Certified to EN54-2 & 4 by the LPCB.
Mains supply 230V 50/60Hz.
Mains rated current 350mA maximum.
Internal power supply 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
Total output current limited to 1.5A @ 230Vac (ImaxA eq 146mA).
Quiescent current
25mA (mains failed, internal sounder active, PSU & gen fault LED lit).
Max battery size and type
2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
No. of detector zone circuits
The CFP702-2 has 2 AlarmSense zone circuits which are compatible with Apollo's AlarmSense range of detectors & call points AND sounders & visual indicators. (Max. length per circuit is 500m).
Call point resistor value
Only use AlarmSense call points.
Max. devices per detector zone
25 AlarmSense detectors/manual call points per AlarmSense zone. For AlarmSense sounder limitations per AlarmSense zone see 'Max. sounder output current' section.
No. of conventional sounder circuits
4 - these are additional conventional (non-AlarmSense) sounder circuits; Max. length per circuit is 500m.
EOL resistor value
6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Alarm voltage
27V max, 20V min (final battery voltage).
Max. sounder output current
Each AlarmSense zone circuit & each conventional sounder circuit will support a max. sounder current of 200mA. Distribute sounder loads as evenly as possible. Total sounder loading per panel should not exceed 1.25A.
Auxiliary relays
Two: (1) Aux. Fire; (2) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Open collector outputs
Two: (1) Reset (Active during reset cycle); (2) Remote (Active during any unsilenced fire condition provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltage 27Vdc).
Other outputs
24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed).
Auxiliary inputs
Two: (1) ‘Class Change’ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
Engineer (AL3) functions
Program coincidence (double knock); Invoke One Man Walk Test; Program delays; Set up zones for non-latching operation; Program sounders to resound (or not resound) when a new zone enters alarm; Enter fault diagnostic facilities.
Expansion connections
Yes - for optional network driver cards (one required per repeater system), relay output cards and EN54-13 sounder circuit interface boards.
Product dimensions (mm)
380 W x 235 H x D 96mm.
Construction & finish
Plastic lid and base; RAL7035 textured.
IP Rating
IP30.
Weight 1.75kg without batteries.
Product dimensions 367 W x 235 H x 96 D mm.
Hole required for flush mounting 367 W x 220 H x 75 D mm. No bezel required.
USEFUL FILES AND LINKS
Videos
Files
  C-TEC CFP708-2 Datasheet
Links*
C-TEC website
C-TEC support site

* External websites provide additional content that supports the content on connectec.uk however the external Web site is subject to change and is beyond the control of Connectec Ltd. Connectec cannot guarantee the accuracy of content on external websites and does not endorse the information or products on any external websites. You will be subject to the external websites own privacy policy when you follow these links.

QUESTIONS AND ANSWERS

Get expert answers to questions specific to this product below or for more help visit our Q&A forum


Do you need to use (Red) glands when wiring into C-TEC Control Panel
( )
Ideally you should use red glands when using red fire cable.
( )
REVIEWS

Read customer reviews or submit your review of this product


Thanks for taking the time to review this product.
Your feedback helps us improve our products and services as well as helping other users make informed buying decisions.

There are no reviews for this product.


Why buy from Connectec?

Support

SUPPORT

Our technical support team are experienced installation engineers with years of field experience.

service_icon.png

SERVICE

Customer service is our top priority. We always try to ensure we offer a first class service too all our customers.

free_delivery_icon.png

DELIVERY

We offer FREE mainland UK delivery on orders over £75 and FREE next day delivery on orders over £150*.

partner_icon.png

PARTNERS

We are approved resellers for direct access to manufacturer warranty and support.

* Qualifying products only, subject to terms. For more information view our delivery information.

Compare 0
Google review badge